According to the DLMS/COSEM Blue Book Ed 12th, section 4.3.6 Profile generic, for the selective access parameters the numbering of entries and selected values starts from 1. But in the ReadRowsByEntry function, of the GXDLMSClient.cpp file, it is shown that the column starts at 0 and not at 1 for the SN context:
Standard says that value should be 1. We are reading one meter that was expecting that value was 0. I check this yesterday and that is now fixed for the firmware of the meter.
We'll change this to 1 also when short name referencing is used.
Question in function ReadRowsByEntry in GXDLMSClient.cpp
Hi Cristian,
Standard says that value should be 1. We are reading one meter that was expecting that value was 0. I check this yesterday and that is now fixed for the firmware of the meter.
We'll change this to 1 also when short name referencing is used.
BR,
Mikko