I have used DLMS director to connect with my smart meter. I'm getting certain objects with abnormal OBIS codes. My understanding is, OBIS codes normally end with 255. But i'm getting some objects that has OBIS codes which end with 101.102,103 etc.'
Please have a look into the picture that i have attached. Please help me in knowing whether it is a normal scenario or an abnormal one.
OBIS code "1.0.1.8.7.101" is correct. Last digit 101 tells the amount of billing periods. I notest that value is not shown here. $(F-100) Should be 1. I added issue from this: http://www.gurux.fi/node/6644
abnormal obis code
Hi,
OBIS code "1.0.1.8.7.101" is correct. Last digit 101 tells the amount of billing periods. I notest that value is not shown here. $(F-100) Should be 1. I added issue from this:
http://www.gurux.fi/node/6644
BR,
Mikko