When trying to connecte Secure meter (premium 300) (indian manufacturer) in HIGH authentication we are getting the following error.
Error : ServiceError Write Exception: Service unsupported.
Gurux GXDLMSDirector: 8.0.1708.1801
Manufacture settings:
Flag ID:EHL
Name: Secure meter
Using logical name referencing: checked
keepinterval: 40
start protocol: DLMS
Addressing:
authenticatoin:none
client address
address(hex):30
server address
address type:Default
serial number formula
physical:1
logical:0
Device properties:
name:secure
manufacture:Secure meter
Logical name referencing:checked
start protocol:DLMS
media:serial
authentical:HIGH
password:3333333333333333
waittime:7
client address: 10
address type:default
physical address:1
logical address:0
settings
serial port:COM11
Trace:
GXDLMSDirector 8.0.1708.1801
Log created 10:51:30
10:52:50 Initializing serial connection.
10:52:50 Send SNRM request.
7E A0 07 03 61 93 69 47 7E
10:52:50 Received data
7E A0 20 61 03 73 05 9E 81 80 14 05 02 02 00 06 02 02 00 07 04 00 00 00 01 08 04 00 00 00 01 6F EF 7E
10:52:50 Parsing UA reply.<CR><LF>81 80 14 05 02 02 00 06 02 02 00 07 04 00 00 00 01 08 04 00 00 00 01
10:52:50 Parsing UA reply succeeded.
10:52:50
7E A0 4C 03 61 10 58 27 E6 E6 00 60 3E A1 09 06 07 60 85 74 05 08 01 01 8A 02 07 80 8B 07 60 85 74 05 08 02 02 AC 12 80 10 78 6B 32 11 3C 2B 46 51 4F 51 1F 44 77 2F 79 5B BE 10 04 0E 01 00 00 00 06 5F 1F 04 00 40 1E 1C FF FF 17 30 7E
10:52:50 Received data
7E A0 58 61 03 30 07 51 E6 E7 00 61 4A 88 02 07 80 89 07 60 85 74 05 08 02 02 AA 12 80 10 31 6A 26 9A 31 6A 26 9A 31 6A 26 9A 31 6A 26 9A A1 09 06 07 60 85 74 05 08 01 01 A2 03 02 01 00 A3 05 A1 03 02 01 0E BE 10 04 0E 08 00 06 5F 1F 04 00 00 18 1C 02 00 00 07 83 0D 7E
10:52:50 Authenticating
7E A0 2B 03 61 32 8D EB E6 E6 00 C3 01 C1 00 0F 00 00 28 00 00 FF 01 01 09 10 DC 81 21 8C FA 34 4E C4 BA BA 37 0F 41 7A CC 31 9B 46 7E
10:52:50 Received data
7E A0 10 61 03 52 7C E2 E6 E7 00 0E 06 03 02 91 24 7E
Gurux.DLMS.GXDLMSConfirmedServiceError: ServiceError Write exception. Service Unsupported
at GXDLMSDirector.GXDLMSDevice.InitializeConnection()
at GXDLMSDirector.MainForm.Connect(Control sender, Object[] parameters)
ServiceError Write Exception: Service Unsupported
Hi,
It seems that your meter is not supporting High authentication level. You should verify this from the meter manufacturer.
BR,
Mikko