Hii Mikko,
I want to know meter type of the DLMS meter using OBIS code. In India, it seems that obis code for meter type is 0.0.94.91.0.255 so, when I tried to read two different types of meters (Secure premier 300 3P-4W and Genus single phase) on gurux director, meter type value for 3P-4W is 3 and for single phase meter is 5. For my application, I need to know the meter type beforehand, so while reading meter parameters, I can send OBIS code accordingly. May I know what are the different values for meter types using above OBIS code. IN, IS15959 , it is given that for 3P-3W value will be 0 and 3P-4W value will be 1 for meter type. But for 3P-4W secure preimer 300, I get meter type value as 3. I am confused about this.
Please let me know about this issue.
Hi Mikko,
It was mistake from my side that I mentioned 0.0.94.91.0.255. Actually I tried reading 0.0.94.91.9.255, but it gave me value 3 as a meter type. Also, what values can be expected for single phase DLMS meter?
Hi Omkar,
Hi Omkar,
0.0.94.91.0.255 is Cumulative Tamper Count. Meter Type is 0.0.94.91.9.255.
0 indicates 3P-3W and 1 indicates 3P-4W
BR,
Mikko
Hi Mikko,
Hi Mikko,
It was mistake from my side that I mentioned 0.0.94.91.0.255. Actually I tried reading 0.0.94.91.9.255, but it gave me value 3 as a meter type. Also, what values can be expected for single phase DLMS meter?
Regards,
Omkar
Hi Omkar,
Hi Omkar,
You need to ask this from the meter vendor. As fas as I know only values 1 and 2 are used.
BR,
Mikko