Hi,
I'm trying to communicate with a meter ( Elster themis-uno EI6) in DLMSDirector.
With authentication "none" I have some response, but i can't reach obis for current index and many other needed.
Using authentication "none" and at the tab secure connection using "encryption" , system tile ( client system tile for management 8 bytes) , block cipher and authentication key same hex code for this specific meter , I get an error "Connection is permanently rejected . Authentication failure"
Can you help me with some info in order to get all the data from obis?
I want to mention that, meter name( series) and only one key(hex) is use in meter tools software and there I have access to all obis.
thank you
Secured settings are used to secure (ciphering) the connection between the meter and the client.
I believe that you want to change authentication level.
Change authentication from None to Low and set the correct password.
I believe that you need also to change the client address. That depends on the meter and can be anything. You need to ask that from the meter vendor.
Hi,
I am using c code from our DLMS source.
here, while reading profile generic(OBIS code: 1,0,99,1,0,255), adding more than 6 object shows "unacceptable frame error" in gurux dierector. but less than 6 is working fine.
please give me specific details about frame generation, if it had.
serial data is pasted below.please find it.
thank you
received data
Please, create a new topic if you have a new question. Can you read your meter with GXDLMSDirector and send trace. I need to send and received messages to tell why your meter is not replying.
DLMS is standard and all frames are described on the standard specifications.
Hi,
Hi,
Secured settings are used to secure (ciphering) the connection between the meter and the client.
I believe that you want to change authentication level.
Change authentication from None to Low and set the correct password.
I believe that you need also to change the client address. That depends on the meter and can be anything. You need to ask that from the meter vendor.
BR,
Mikko
Hi,
Hi,
I am using c code from our DLMS source.
here, while reading profile generic(OBIS code: 1,0,99,1,0,255), adding more than 6 object shows "unacceptable frame error" in gurux dierector. but less than 6 is working fine.
please give me specific details about frame generation, if it had.
serial data is pasted below.please find it.
thank you
received data
7E A0 1E 21 03 73 C3 7A 81 80 12 05 01 80 06 01
80 07 04 00 00 00 01 08 04 00 00 00 01 53 3B 7E
000123: 2020-02-20 12:41:34.0261099 +0.0000032
7E A0 37 21 03 30 6C 7C E6 E7 00 61 29 A1 09 06
07 60 85 74 05 08 01 01 A2 03 02 01 00 A3 05 A1
03 02 01 00 BE 10 04 0E 08 00 06 5F 1F 04 00 00
1E 1D 01 64 00 07 9B AE 7E
000143: 2020-02-20 12:41:36.4474746 +0.0000039
7E A8 86 21 03 52 7F 1B E6 E7 00 C4 01 C1 00 01
07 02 04 12 00 08 09 06 00 00 01 00 00 FF 0F 02
12 00 00 02 04 12 00 03 09 06 01 00 01 07 00 FF
0F 02 12 00 00 02 04 12 00 03 09 06 01 01 20 07
00 FF 0F 02 12 00 00 02 04 12 00 03 09 06 01 01
34 07 00 FF 0F 02 12 00 00 02 04 12 00 03 09 06
01 01 48 07 00 FF 0F 02 12 00 00 02 04 12 00 03
09 06 01 00 1F 07 00 FF 0F 02 12 00 00 02 04 12
00 03 09 06 01 EC B9 7E
000181: 2020-02-20 12:41:36.6270586 +0.0000027
7E A0 13 21 03 54 F1 A4 00 33 07 00 FF 0F 02 12
00 00 F7 BC 7E
000201: 2020-02-20 12:41:40.6745081 +0.0000028
7E A0 18 21 03 76 F4 66 E6 E7 00 C4 01 C1 00 09
06 01 00 63 01 00 FF E3 E6 7E
000221: 2020-02-20 12:41:40.7964356 +0.0000031
7E A0 15 21 03 98 0B E3 E6 E7 00 C4 01 C1 00 06
00 00 00 3C 92 E3 7E
000241: 2020-02-20 12:41:40.9600120 +0.0000040
7E A0 07 21 03 97 2B E1 7E
000261: 2020-02-20 12:41:44.9338210 +0.0000032
7E A0 1E 21 03 73 C3 7A 81 80 00 05 01 80 06 01
80 07 04 00 00 00 01 08 04 00 00 00 01 D9 69 7E
sent data
7E A0 07 03 21 93 0F 01 7E 7E A0 07 03 21 93 0F
01 7E
000108: 2020-02-20 12:41:33.8509986 +0.0001978
7E A0 2B 03 21 10 FB AF E6 E6 00 60 1D A1 09 06
07 60 85 74 05 08 01 01 BE 10 04 0E 01 00 00 00
06 5F 1F 04 00 00 1E 1D FF FF C5 E4 7E
000128: 2020-02-20 12:41:36.2138230 +2.1864271
7E A0 19 03 21 32 6F D8 E6 E6 00 C0 01 C1 00 07
01 00 63 01 00 FF 03 00 8C 90 7E
000166: 2020-02-20 12:41:36.4601495 +0.0005036
7E A0 07 03 21 51 11 E4 7E
000186: 2020-02-20 12:41:40.5396242 +3.9119431
7E A0 19 03 21 74 5D FF E6 E6 00 C0 01 C1 00 07
01 00 63 01 00 FF 01 00 3C A3 7E
000206: 2020-02-20 12:41:40.6758782 +0.0008041
7E A0 19 03 21 96 41 3B E6 E6 00 C0 01 C1 00 07
01 00 63 01 00 FF 04 00 84 DD 7E
000226: 2020-02-20 12:41:40.7991928 +0.0020739
7E A0 4C 03 21 B8 7C 48 E6 E6 00 C0 01 C1 00 07
01 00 63 01 00 FF 02 01 01 02 04 02 04 12 00 08
09 06 00 00 01 00 00 FF 0F 02 12 00 00 09 0C 07
E4 02 14 04 00 00 00 FF FE B6 00 09 0C 07 E4 02
15 05 00 00 00 FF FE B6 00 01 00 0F 8E 7E
000246: 2020-02-20 12:41:44.8175701 +3.8568997
7E A0 07 03 21 53 03 C7 7E
Hi,
Hi,
Please, create a new topic if you have a new question. Can you read your meter with GXDLMSDirector and send trace. I need to send and received messages to tell why your meter is not replying.
DLMS is standard and all frames are described on the standard specifications.
BR,
Mikko