Dear Sir,
I am facing an issue with reading profile generic values as they are not giving values multiplied with scalars.
Gurux application is reading values multiplied with scalar. for eg: voltage 11281*.01=112.81
same while I am trying to read from my code its not showing multiplied values but giving value just as 11281.
Eg: L&G E650
"1.0.94.91.0.255Ch. 0 Identifiers for India" same is having an obis code "1.0.94.91.3.255Ch. 0 Identifiers for India" with scalar and unit.
Please suggest how to do this as it is done internally in GuruX application.
Reading profile generic values
Hi,
At the moment you need to read scaler table first and implement multiple by yourself.
There is no generic solution for this.
BR,
Mikko